Size: 1/8 DIN 48 × 96 × 78(W × H × D).
Power supply voltage: 100 to 240 VAC.
Input type: Thermocouple or Resistance thermometer.
Alarm output: 3.
Control output: Current output E5CN-QQ2HT PDF.
Functions: Heater burnout, No; Mounting option units, No.
Previous model: E5EZ-C3 E5EZ-A3 + E53-AZC.
These Best-selling General,
purpose Temperature Controllers,
Are Now Even Better.
Controllers now available with analog inputs
E5CN-QQ2HT
Faster sampling at 250 ms.
Transfer output provided for easy output to recorders.
Models available with a loop break alarm (LBA) and,
heater short alarm (HS alarm).
Manual output provided E5CN-QQ2HT PDF.
Easy setting with 11-segment displays.
New protocol called Modbus is installed in the,
models with communications.
USB-Serial conversion cable is available.
Note: Refer to Precautions on page 33. Control output: Voltage output.
Auxiliary output: --.
Communications: RS-485.
Heater burnot: -- E5CN-QQ2HT PDF.
Event inputs: --.
Power supply voltage: 100 to 240 VAC.
The E5DC-800 Mounts to DIN Track and Is Ideal,
for Connections to HMIs and PLCs.
It provides the Same Easy Operation and,
Advanced Performance as the Rest of the,
E5@C-800 Series.
A slim body at 85 × 22.5 mm (D × W) that fits into narrow control,
panels and mounts to DIN Track OMRON USER'S MANUAL.
Removable terminal block for easy replacement to simplify maintenance.
High-speed sampling at 50 ms for applications with high-speed,
temperature increases.
Easy connections to a PLC with programless communications.
Models are available with up to 2 auxiliary outputs and 1 event input to,
complete basic functions OMRON USER'S MANUAL.
A white PV display (height: 8.5 mm) is easy to read when setting up,
checking alarms, and making settings in a control panel. High performance price ratio standard type proximity sensor.
Staandard cable protector OMRON USER'S MANUAL E5CN-QQ2HT Manual.
The new DC two-wire type.
Non polar proximity sensor.
Type: DC three wire / wire type.
Shape: shield, M18.
Detection range: 5mm.
Output configuration: NPN.
Action mode: NO. Case color: Black.
Control output: Voltage output (for driving SSR).
Control mode *1: Standard or heating/cooling.
No. of auxiliary outputs: 1.
Detection of heater burnout, SSR failure, and heater overcurrent: --.
No. of event inputs: --.
Transfer output *2: --.
Communi cations: RS-485.
Previous model: Thermocouple input, --;
Resistance thermometer input, --.
New 48 x 24-mm Basic Temperature,
Controller with Enhanced Functions and,
Performance. Improved Indication Accuracy,
and Preventive Maintenance Function.
Indication Accuracy.
Thermocouple input: ±0.3% of PV (previous models: ±0.5%),
Pt input: ±0.2% of PV (previous models: ±0.5%),
Analog input: ±0.2% FS (previous models: ±0.5%),
Models are available with screw terminal blocks or screwless,
clamp terminal blocks.
A PV/SV-status display function can be set to automatically alternate,
between displaying the status of tthe Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV E5CN-QQ2HT USER'S MANUAL.
Preventive maintenance for relays in the Temperature,
Controller using a Control Output ON/OFF Counter.
Switch the PV display between three colorrs E5CN-QQ2HT Manual.
Compatible with Support Software (CX-Thermo version 4.2 or higher).
Eleven-segment displays.
Models are available with one or two alarm outputs.