Size: 48 x 48mm.
Control output 1: voltage output (SSR driver).
Control output 2:--.
Auxiliary output: 2 independent points.
Power supply voltage: AC/DC24V E5CN-RMT-500 PDF.
Terminal type: screw terminal table type.
Input category: full range multi input.
Heater break, SSR fault detection function: -.
Communication: RS-485.
Event input: 1 points.
Remote SP input: -.
Transfer output: -.
Using large font PV display (white), improve visibility
E5CN-RMT-500
Selection, operation and setting.
Functional performance of input and output points.
Support for more extensive range of applications.
Using high PV 15.2mm display (white), improve visibility E5CN-RMT-500 PDF.
High speed sampling to achieve 50ms.
With auxiliary output (maximum 3 points), event input (maximum 4 points), the transmission output,
Remote SP input function, support for a variety of applications.
E5CC 60mm has a depth of slender body.
The use of communication adapter cable (sold separately) connected with a computer E5CN-RMT-500 PDF.
After that, no power supply connection can be set.
It can be easily set by CX-Thermo (sold separately).
Easy to connect with PLC through no program communication.
Combined temperature control device through component communication OMRON User's Manual. E3F3-R37 detection methods: Regression reflection type,
Lead extraction: CN M12,
Type: Plastic appearance; PNP output,
Threaded cylindrical photoelectric sensor, built-in amplifier,
Photoelectric sensor with proximity sensor appearance
High anti interference with optoelectronic -IC technologyCase color: Black OMRON User's Manual E5CN-RMT-500 Manual.
Control output: Voltage output (for driving SSR).
Control mode *1: Standard.
No. of auxiliary outputs: --.
Detection of heater burnout, SSR failure, and heater overcurrent: --.
No. of event inputs: --.
Transfer output *2: --.
Communi cations: --.
Previous model: Thermocouple input, E5GN-QTC;
Resistance thermometer input, E5GN-QP OMRON User's Manual.
New 48 x 24-mm Basic Temperature,
Controller with Enhanced Functions and,
Performance. Improved Indication Accuracy,
and Preventive Maintenance Function.
Indication Accuracy.
Thermocouple input: ±0.3% of PV (previous models: ±0.5%),
Pt input: ±0.2% of PV (previous models: ±0.5%),
Analog input: ±0.2% FS (previous models: ±0.5%),
Models are available with screw terminal blocks or screwless,
clamp terminal blocks.
A PV/SV-status display function can be set to automatically alternate,
between displaying the status of thee Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV E5CN-RMT-500 User's Manual.
Preventive maintenance for relays in the Temperature,
Controller using a Control Output ON/OFF Counter.
Switch the PV display between three colorrs E5CN-RMT-500 Manual.
Compatible with Support Software (CX-Thermo version 4.2 or higher).
Eleven-segment displays.
Models are available with one or two alarm outputs.