Name: Loop-control CPU Unit.
I/O bits: 1,280 bits.
Program capacity: 60K steps.
DM words: 32K words.
EM words: 32K words × 3 banks E0_00000 to E2_32767.
Highest Performance Standards in the Industry.
Unit classification: CJ1 Special I/O Units.
Product name: Temperature Control Units.
Specifications; No. of loops: 4 loops;
Temperature sensor inputs: Platinum ,
resistance thermometer input(JPt100, Pt100);
Control outputs: Open collector PNP outputs (pulses).
No. of unit numbers allocated: 2 OMRON CJ1G-CPU45P.
Current consumption: 5V, 0.25A; 24V, --.
Standards: UC1, N, L, CE.
A Single Unit Performing All the Functions of,
4 Temperature Controllers
CJ1G-CPU45P
A Special I/O Unit with direct input,
of thermocouple or resistance thermometer,
PID control with 2 degrees of freedom,
and open collector output. Unit type: CJ1 Basic I/O Units.
Product name: DC Input Units.
Specifications: I/O points, 32 inputs;
Input voltage and current: 24 VDC, 4 OMRON CJ1G-CPU45P. 1 mA;
Commons, 16 points, 1 common; External connection,
Fujitsu connector; No. of words allocated, 2 word.
Current consumption: 5V, 0.09A; 24V, --.
Standards: UC1, N, L, CE.
A Wide Range of Basic Input,
Units for High Speed Input and,
Different Applications.
Receive ON/OFF signals from external,
devices into the PLC System to update,
I/O memory in the CPU Unit OMRON CJ1G-CPU45P.
New high-speed input models CJ1W-ID212 and,
CJ1W-ID233 are now available. These units can,
help to increase system throughput. Unit type: CJ1 Special I/O Units.
Product name: Analog Output Unit.
I/O points: 2 outputs;
Signal range selection:
Set separately for each output.
Signal range, Resolution: 1 to 5 V,
0 to 5 V, 0 to 10 V, -10 to 10 V,
4 to 20 mA; 1/4,00.
Conversion period: 1 ms/point.
Accuracy at ambient temperature of 25°C:
Voltage: ±0.3% of F.S. Current: ±0.5% of F.S.
External connection: Removable terminal block.
External power suppply: 24 VDC +10% -15%, 140mA max CJ1G-CPU45P.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.12A; 24V, 0.14*3.
Standards: UC1, N, L, CE.
Consistent Microsecond Throughput:
Models with Direct Conversion Join the Lineup.
Anaalog Input Units for converting analog input,
signals into binary data CJ1G-CPU45P.
Analog Output Units for converting binary ,
data into analog output signals.