Master station.
Province distribution network module in cabinet and device.
Link to connect the 64 stations when the fastest scanning time for 1.2ms (rate 2 Q02HCPU-A PDF. 5Mbps).
According to the transmission distance, the transmission rate is selected from 2.5Mbps, 625kbps and 156kbps.
CC-Link/LT from the station does not need any parameter settings.
Only need to set up the transmission speed in the master module, you can use the remote I/O
Q02HCPU-A
QJ61CL12 can be used as the main station of CC-Link/LT.2 axes, open collector output type.
2 axis linear interpolation.
2 axis interpolation.
Control unit: mm, inch, degree, pulse Q02HCPU-A PDF.
Location data: 600 data / axis.
Maximum pulse output: 200Kpps.
40 pin connector.
Positioning module.
Open collector output.
Differential driver output.
Based on the use of open collector outputs and differential drive output type 2 types.
Differential driver output type positioning module can transmit high speed instruction pulse (up to 4Mpps) to the servo amplifier reliably,
Transmission distance of up to 10 meters, to achieve high speed and high precision control Q02HCPU-A PDF.
(the command pulse of the open collector positioning module is highest 200kpps.) Battery replacement.
Initial voltage 3 MITSUBISHI Programming Manual. 0V.
Service life: 5 years.High speed data communication module.
10BASE-T/100BASE-TX.
Real time transmission control data, to improve the production efficiency and the value of the equipment to provide support for the high-speed data communication module.
The high accuracy data that can be synchronized with the sequential scanning to the user program on the PC can be transmitted through the Ethernet MITSUBISHI Programming Manual.
Realize the previous communication method can not achieve the detailed control of data transmission,
Real time data analysis using user applications,
In order to provide support for improving production efficiency and equipment value MITSUBISHI Programming Manual. Output points: 16 points.
Output voltage and current: DC12~24V; 0.5A/ point; 4A common.
OFF leakage current: 0.1mA.
Response time: 1ms.
16 points and 1 common ends.
Leaky type.
18 point terminal station.
With the surge absorber.
With fuse.
Ultra high speed processing, production time is shortened, better performance.
As applications become larger and more complex, it is necessary to shorten the system operation cycle time.
The operation period can be shortened by the super high basic operation speed 1.9ns.
In addition to achieve in the past with the control of single-chip high-speed control,
The system performance can be improved by reducing the total scan time,
To prevent any possible performance bias.
Convenient processing of large capacity data.
In the past can not achieve the standard RAM and SRAM card file register area of continuous access,
The boundary of each area should be considered in programming.
The SRAM 8MB extension card is installed in the hiigh speed universal QCPU,
Standard RAM can be used as a continuous file register,
Capacity up to 4736K words, thus simplifying the programming Q02HCPU-A Manual.
Thus, even if the memory space of the soft element is insufficient,
Can also be installed by the expansion of SRAM card, easy to extend the file register area.
The address register is extended to 32 bits, which can be programmed to go beyond the traditional 32K word,
And to achieve the extension to the file register to all regions of the file register.
In addition, the processing speed of the index modification plays an important role in the efficient operation of structured data (array),
The speed has been improved.
When the index is used to modify the program repeatedly (e.g. from FOR to NEXT), the scan time can be reduced.
With the help of sample tracking function, the starting time is shortened
By using the sampling and tracking function, it is convenient to analyze the data when the fault occurs,
Testing procedures for the time, etc., can shorten the time of failure analysis and start-up time.
In addition, the multi CPU system also helps to determine the daata transceiver time between the CPU module Q02HCPU-A Programming Manual.
Can be used to analyze the data collected by programming tools,
In the form of charts and trend charts, the data changes of the bit soft element and the word soft element can be easily diisplayed Q02HCPU-A Manual.
And the sampling tracking results can be stored in LogViewer GX form CSV,
By recording data display and analysis tool LogViewer GX to display.