Unit classification: CJ1 Special I/O Units.
Product name: Temperature Control Units.
Specifications; No. of loops: 4 loops;
Temperature sensor inputs: Thermocouple,
input (R, S, K, J, T, B, L);
Control outputs: Open collector PNP outputs (pulses) CJ1W-NC213 PDF.
No. of unit numbers allocated: 2.
Current consumption: 5V, 0.25A; 24V, --.
Standards: UC1, N, L, CE.
A Single Unit Performing All the Functions of,
4 Temperature Controllers
CJ1W-NC213
A Special I/O Unit with direct input,
of thermocouple or resistance thermometer,
PID control with 2 degrees of freedom,
and open collector output. C500-DA/3G2A5-DA Special I/O Unit Analog Output C500-DA002(3G2A5-DA002) CJ1W-NC213 PDF.
Output: 2 pts.
Specification: 0~+10V.Product name: CS1 CPU Backplane.
Specifications: For CS-series,
Unit only Note: C200H series,
Units cannot be mounted; 3 slots.
Appli cable CPU Unit: CS1 CPU Unit.
Basic I/O Units: CS-series Basic I/O Unit,
Yes; C200H series Basic I/O Unit, No;
C200H Group-2 High density I/O Unit, No CJ1W-NC213 PDF.
Special I/O Units: CS-series Special I/O Unit,
Yes; C200H series Special I/O Unit, No.
CPU Bus Units: CS-series CPU Bus Unit, Yes.
Current consumption: 5V system, 0.11A;
26 V system, --.
Standards: U, C, N, L, CE OMRON PROGRAMMING MANUAL.
Multi-application Controllers:
From High-performance Machine C,
Highly Reliable Process Control. For C200H-PRO27-E Hand-held Programming Console ming Console.
2m.ID Sensor Units
The ID Sensor Unit is a non-contact ID system thaat unifies product, production, and control data, and provides for efficient production of different products in varying quantities OMRON PROGRAMMING MANUAL CJ1W-NC213 Manual. A separate catalog is available providing information aboutModel: C200H-OD213.
No. of points: 8 pts.
Specifications: 2.1 A, 24 VDC.Unit classification: CJ1 Special I/O Units.
Product name: Process Input Units,
(Isolated type Units with Universal Inputs) OMRON PROGRAMMING MANUAL.
Input points: 4 inputs.
Signal range selection:
Set separately for each input.
Signal range:Fully universal
inputs: Pt100, JPt100, Pt1000, K,
J, T, L, R, S, B, 4 to 20 mA, 0 to 20 mA,
1 to 5 V, 0 to 5 V, 0 to 10 V.
Conversion speed (resolution): Conversion,
speed: 250 ms/4 inputs.
Accuracy at ambient temperature of 25°C:
Accuracy: Platinum resistance thermometer,
input: ±0.3% of PV or ±0.8°C, whichever,
is larger) ±1 digit max. Thermocouple input:
(±0.3% of PV or ±1.5°C, whichever is larger),
±1 digit max. *1 Voltage or current input:
±0.3% of F.S. ±1 digit max.
External connection: Removable terminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0 CJ1W-NC213 PROGRAMMING MANUAL. 32A; 24V, --.
Standards: UC1, L, CE.
A Single Unit Handling All Types of Inputs,
such as Temperature Sensor Inputs and,
Analog Signal Inputs (e.g., 4 to 20 mA or 1 to 5V).
A Unit supports four inpuut channels,
each of which can be set to a
platinum resistance thermometer, thermocouple,
and DC signal (current, voltage) CJ1W-NC213 Manual.
All inputs are isolated.