Isolation method: Relay.
Zero cross function: No.
Operation indicator: Yes.
Applicable output load(See note.): 10 A 100 to 240 VAC.
Rated input voltage: 24 VDC GRT1-END PDF.
Hybridization of a Magnetic Relay and an,
SSR Achieves 10-A Switching for 10 Million,
Operations.
UL/CSA certified (-VD models).
Using a triac to open and close the circuit reduces chattering,
and arching, thereby increasing the electrical durability to 10,
million operations
GRT1-END
Relays contacts for power ON and 10-A switching with high,
capacity are provided in a compact body without the need of,
radiators. Plus, there is almost no effect on heat generation,
or ambient temperature GRT1-END PDF.
Operation indicators to easily check operation.
Built-in temperature fuse prevents internal burning due to,
triac or relay malfunctions.
Socket-type Relays the same size as the 1-pole and 2-pole,
LY Relays. Cable with connector (1 to 2) /G79-I_-_-D1,
G79-O_-_-D1, G79-M_-_-D1 GRT1-END PDF.
Size: A, 750mm; B, 500mm.
Cable and loose wire cable with loose wire pressing connecting terminal,
Connector cable, MITSUBISHI motor produced PLC connection cable. Applicable I/O Relay Terminal: G70V-SOC16P-1.
Type: Output.
Internal I/O circuit common: PNP (- common) OMRON REFERENCE MANUAL.
Rated voltage: 24 VDC.
I/O Relay Terminals with 16 Points and,
Push-In Plus terminal blocks to,
Downsize Control Panels and Save Labor.
I/O Relay Terminals with 16 points to mount G2RV Slim I/O Relays.
Push-In Plus terminal blocks are used to save wiring work in,
comparison with traditional screw terminals OMRON REFERENCE MANUAL. (Wiring time is,
reduced by 60%* in comparison with traditional screw terminals.).
Work is reduced ever further with one-step cable connection to the PLC.
Diode provided for coil surge absorption.
Operation indicators for immmediate recognition of I/O signal status OMRON REFERENCE MANUAL GRT1-END Manual.
Accepts G3RV Slim I/O SSRs.
DIN Track or screw mounting. Input capacity: 32 points.
Rated current (ON current): 0.5 A/output, 4.0 A/common.
Internal I/O common: NPN.
Residual voltage: 1.2 V max. (0.5 ADC,
between each output terminal and the G terminal).
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common: 16 points/common.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Output device supply current: 100 mA/point.
Unit power supply current consumption: 100 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 210 g max.
Expansion functions: No.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common termiinal is provided for,
each connector GRT1-END REFERENCE MANUAL.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software GRT1-END Manual.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.