Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min.
(between each input terminal and the G terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the G terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC) .
ON delay: 0.1 ms max.
OFF delay: 0 G8ND-2S DC12 SK. 2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms
G8ND-2S DC12 SK (Default setting: 1 ms)
Number of circuits per common: 8 points/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Input device supply current: 100 mA/point G8ND-2S DC12 SK.
Unit power supply current consumption: 90 mA max .
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max.
Expansion functions: No.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks G8ND-2S DC12 SK.
It is unnecessary to share the common terminal,
among multiple contacts .
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenance. Name: Temperature Controller (See note 1.).
Power supply: 24 VDC.
No. of control points: 2.
Control output: Voltage output (for SSRs).
Auxiliary output: Transistor output: 2 pts (sourcing).
Functions: Heater burnout alarm (See note 3.), Heating or heat/cool,
control is selectable (See note 4.)Event input: 1 point per Unit.
Communications functions: RS-485.
Input type (See note 5.): Platinum resistance thermometer.
New DIN Track Mounting Temperature.
Controller.
Two channels of temperature control available despite width of,
only 22.5 mm.
The Temperature Controller itself caan be replaced without,
changing terminal wiring G8ND-2S DC12 SK.
Use in combination with a compact Setting Display Unit to,
reduce communications programming requirements.
Front-panel LED indicators for easy operation monitoring.
Power supply and communicatiionns wiring not required between,
Units when mounted side-by-side G8ND-2S DC12 SK.
CompoWay/F communications protocol supported.
UL, CSA, and CE Marking compliance.
G8ND-2S DC12 SK Operation manual / Instructions / Catalog download link: