The main body: terminal type, temperature input type.
Category: control output 1 point type (power supply AC100 ~ 240V).
Shell color: black.
Control output: relay output.
Control mode: standard or heating cooling.
Auxiliary output points: 2 points.
A power supply for the detection of /ES1B fault, SSR fault and heater over current for heater use D5B-5013.
Event input points: -.
Transfer output: -.
Communication: -
D5B-5013
48mm general thermostat has been upgraded & function / performance upgrade.
Indicates that the accuracy is increased and the preventive maintenance function is increased,
Further performance improvement.
E5CN-U (insert type) add analog input and current output type D5B-5013.
Add PV/SV status display function, convenient to check the state of the thermostat (automatic / manual, RUN/STOP, alarm),
Interactive display PV/SV .
Increase the number of control output ON/OFF counting function, can prevent the maintenance of temperature controller internal relay. Sensing method: Reflective model(for mark detection).
Connection method: Pre-wired (2 m) D5B-5013.
Sensing distance: 30±5 mm .
Extremely thin beam ideal for detection of minute objects and marks.
Ideal for detection of small objects and slight color differences.
Bad mark detection.
Detection of thin wire of 200 μ.
Detection of slight level differences. Case color: Black.
Control output: Voltage output (for driving SSR).
Control mode *1: Standard or heating/cooling.
No. of auxiliary outputs: 2.
Detection of heater burnout, SSR failure, and heater overcurrent: --.
No. of event inputs: 2.
Transfer output *2: --.
Communi cations: --.
Previous model: Thermocouple input, --;
Resistance thermometer input, --.
New 48 x 24-mm Basic Temperature,
Controller with Enhanced Functions and,
Performance. Improved Indication Accuracy,
and Preventive Maintenance Function.
Indication Accuracy.
Thermocouple input: ±0.3% of PV (previous models: ±0.5%),
Pt input: ±0.2% of PV (previous models: ±0.5%),
Analog input: ±0.2% FS (previous models: ±0.5%),
Models are available with screw terminal blocks or screwless,
clamp terminal blocks.
A PV/SV-status display function can be set to automatically allternate,
between displayinng the status of the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV D5B-5013.
Preventive maintenance for relays in the Temperature,
Controller using a Control Output ON/OFF Counter.
Switch the PV display between three colorrs D5B-5013.
Compatible with Support Software (CX-Thermo version 4.2 or higher).
Eleven-segment displays.
Models are available with one or two alarm outputs.
D5B-5013 Operation manual / Instructions / Catalog download link:
/searchDownload.html?Search=D5B-5013&select=5