FX3U 4AD 4DA application example

Time: 9/12/2017 6:13:30 AM

See the Fnalog FX3U-4AD manual, FX3U-4AD he and FX2N analog module is not the same, like the FROM and TO instructions is not very good, MITSUBISHI provides a method in mov to read and write instructions, you cannot read, and can I cite a simple example? Thank you
Re:   Time: 9/12/2017 10:26:00 PM
Used in Mstructions, FX3U-4DA such FX3U-4DA as U0\G0:
U0 stands for the special function module number, equivalent to the first operand in the FROM and TO instructions. U0 is the first special function module of PLC extension, and if U1 is the second special function module of PLC extension.
G0 represents the buffer memory number of the special function module, equivalent to the second operands of the FROM and TO instructions. G0 is a special function