How to set up the default 8 high speed counters

Time: 4/26/2017 6:32:09 PM

I use the-128MR speed counters programmer, speed counters I now need 8 high speed counter, but the programming is the default 6, C235-C240 defaults to X0-X5, I want to use 8, can you tell me how to set the X6 X7 also can make the default for the high speed counter input default counter is C244, C245
Re:   Time: 4/27/2017 2:19:00 AM
The basic unit of FX2N can only be used at most 6 high speed counters, plus 2 high speed counting module FX2N-1HC can be connected to 2 high speed counting.