K2GS-BP-R2 OMRON Ground directional relay series

Brand: OMRON
Name: Ground directional relay series
Model: K2GS-BP-R2
A collection of shell: the shell embedded R2 shell.
Purpose: high voltage PC (reactor) grounding system.
Static ground directional relay K2GS-B type,
Advanced ground direction relay corresponding to the diversification of ground fault.
Feeder priority cut-off function for coordinated multi segment setting.
Prevention of low frequency vibration with other circuit accidents,
Circuit for locking circuit and preventing effect of electric wave caused by false action,
In order to improve the reliability.
The coordination device for the zero phase action voltage is set up,
Therefore, the influence of the residual voltage can be avoided.
Due to the built-in filter, so in the event of the occurrence of the ramp wave input can also maintain a stable role,
Because of the signal level detection, it is easy to carry out the action experiment and set up the confirmation.

Appearance: insert type.
Control supply voltage: DC100/110V.
Action elements: overload detection.
Action characteristic: instantaneous action type.
Especially suitable for single phase motor over current protection.
Can be used for motor overload protection, common single-phase circuit of the AC current detection K2GS-BP-R2 OMRON.
A variety of models, such as anti time limit characteristics, lock time, instantaneous action, etc K2GS-BP-R2, are provided,
The product is rich in variety, and can be effectively protected, detected and controlled according to the actual situation.
When the current is large, the input resistance of the CT or the relay part is not needed, and the use is simple.
Because it is a plug-in, installation, disassembly, wiring and other operations are very simple K2GS-BP-R2 OMRON. Type: Medium-sensitivity models.
Sensed current: 500 mA/1,000 mA(switchable).
Type: High-speed models.
Operating time: Less than 0.1 s.
Economical, Compact, High-performance,
DIN 48 × 48-mm Ground Fault Relay for Low,
Voltages.
Performs continuous monitoring and detection of ground faults,
in low-voltage circuits due to the deterioration of insulation in,
electrical devices K2GS-BP-R2 OMRON.
Higher reliability ensured with improved resistance to high-fre,
quency noise when used for inverter loads.
Ground Fault Relays and through-type ZCTs (zero-phase current,
transformers) are mutually compatible.
The through-type ZCTs are equipped with test terminals,
allowing operation tests for Ground Fault Relays to be performed withease. Appearance: there are F4 shell, R2 shell.
Circuit structure and open circuit mode: constant circuit contact, secondary current circuit breaker.
Rated current: AC5A.
Rated frequency: 50/60Hz (switching).
Current adjustment range: time limit elements: 3-3.5-4-4.5-5-6A, 6 shunt;
Instantaneous elements: 20-30-40-50-60A-, 6 shunt.
Action time: time limit element time to adjust the degree 0.25-0.5-1-2-3-4-5-6-7-8-9-10,
12 nominal action time to adjust the scale of 10300% over current, 10s plus or minus 5%,
700% over current, 1.52s plus or minus 7%; instantaneous elements, nominal action time 200% over current 40ms.
Control power supply: do not.
Rated consumption VA:6VA.
Contact capacity: AC12V, 60A (CT secondary current) 100 times; AC20V, 100A (CT secondary current) 3 times.
Contact: AC110V, 7.5A, COS with =0.4; (AC250V 825VA)
DC24V, 5A, L/R=7ms (maximum 50W time DC125V).
Automatic experiment: No.
Display: start display (LED), after the time display (LED).
Output display, trip (R phase and T phase) manual reset type, instant manual reset type.
Excitation surge current suppression (fuzzy inference): -.
Quality: about 1.3KG (R2 shell), about 1.8kg (F1 shell), about 3.3kg (D2 shell).
External: Mount Searl N1.5.
Static type over current relay K2CA-D type, attention to the protection of the coordination of static type OCR.
The protection cooordination between OCR and MCCB is simple K2GS-BP-R2.
1 sets of three-phase protection, can save space and manpower.
Compared with the plate movement start display, through time display, make maintenance and inspection becomes simple.
The display oof the accident occurrence phase is used to facilitate the inspection after the accident K2GS-BP-R2.
Reduce the consumption of VA, reduce the burden of converter.