LK166
Home >> Products >> MITSUBISHI >> R series PLC >> Motion / position / high speed counter module >> MITSUBISHI RD62P2E High speed counter module

MITSUBISHI RD62P2E High speed counter module

Brand: MITSUBISHI
Name: High speed counter module
Model: RD62P2E
DC input, transistor (source) output.
Channel number: 2CH.
External wiring connection mode: 40 pin connector
Count input signal: there
Single phase input (single frequency / double frequency)
Dual phase input (single frequency and double frequency /4)
CW/CCW input: there
The signal level (phi A, Phi B): 2 ~ 5mA DC5/12/24V.
Pulse measurement function can be measured by measuring the pulse ON/OFF time and cycle, the length and speed of the workpiece.
For example, in the production of food, beverages, the use of proximity sensors to measure the size and speed of the bottle on the conveyor.

The input power supply voltage: AC100 ~ 240V.
Input frequency: 50/60Hz plus or minus 5%.
Input maximum apparent power: 130VA.
Maximum input power: -.
Rated output current (DC5V): 6.5A.
Rated output current (DC24V): -.
IQ-R MELSEC series consists of CPU module, power module, substrate module, input and output module, intelligent function module and so on MITSUBISHI RD62P2E.
For the entire system, the substrate module can be expanded to 7 levels, up to 64 modules can be installed,
Therefore, large scale system can be constructed RD62P2E In addition, by using the RQ extended substrate module,
The sea can also effectively use the MELSEC-Q series of modules of the asset. "Analog input channel number: 16CH.
accuracy
Ambient temperature of 25 plus or minus 5 degrees C: plus or minus 0 MITSUBISHI RD62P2E. 1%.
Ambient temperature 0 ~ 55 degrees C:-.
Temperature coefficient: positive and negative 35ppm/.
Common
Conversion speed: 10ms.
Insulation between channels: isolation transformer insulation.
Absolute maximum input: positive and negative 15V, 30mA.
External wiring connection: 40 pin connector two.
Voltage input
The analog input voltage: DC - 10 - 10V MITSUBISHI RD62P2E.
Digital output value: 32000 ~ 32000.
Current input
Analog input current: DC0 ~ 20mA.
Digital output value: 0 ~ 32000.
Execute event driven program through alarm output
Strengthen the implementation of the interrupt function according to the alarm output flag, easy to carry out preventive maintenance.
The measured value and the change rate of the analog input signal exceed the upper and lower limits of the set,
Regardless of the procedure of the scan time, can be executed interrupt handling, quickly respond to abnormal conditions.
Analog input module for the external analog signal into the interface of the programmable controller.
Can choose the channel between the insulation, voltage input, current input, voltage / current mixed input, thermocouple input, temperature resistance (RTD) input for a variety of purposes, such as modules RD62P2E.
Filter high frequency interference.
Analog input module has been equipped with a first order lag filter.
The analog input signal with high frequency interferencee component can be obtained by using the first order lag filter RD62P2E.
Parameters can be set through the filter time constant, no program can be easy to use.