Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min.
OFF voltage: 5 VDC max.
OFF current: 1.0 mA max.
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
2 ms, 4 ms, 8 ms, 16 ms, 32 ms. (Default setting: 1 ms)
Number of circuits per common: 8 points/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Input device supply current: 100 mA/point.
Unit power supply current consumption: 90 mA max.
I/O power supply current consumption: 5 mA max.
Weight: 370 g max.
Expansion functions: No.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks.
among multiple contacts.
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance.
Input response time can be switched for high-speed processing.
switch and with tool software.
node identification becomes possible for maintenance.
Input capacity: 16 points.
Rated current (ON current):
0.5 A/output, 4.0 A/common.
Internal I/O common: NPN.
Residual voltage: 1.2 V max.
(0.5 ADC, between each output,
terminal and the G terminal).
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common: 16 points/common OMRON GX-ID1622.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation
GX-ID1622
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled OMRON GX-ID1622.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit.)
Input/output point can be flexibly increased,
depending on the system OMRON GX-ID1622.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance. Classification: Analog input.
I/O points: 4 inputs (Resolution: 30, 000).
Performs Calculations on Analog Values within the Slave Itself.
Also Provides High Resolution at 1/30,000 (Full Scale) and,
Support for a Wide Variety of Data Sampling.
Equipped with the standard Smart Slave functions that provide powerful,
preventative maintenance and troubleshooting capabilities.
Sampling data can be analyzed internally to provide a low-cost scheduler funnction GX-ID1622.
Equipped with functions such as the scaling function, peak/bottom hold;
top/valley hold; comparator function, cumulative counter, and derivative,
calculation function.
Two I/O points can be allocated to any two of the followingg values: analog,
input, peak/bottom, top, valley, or rate-of-change GX-ID1622. Values without an,
allocated I/O point can be read with message communications.