AnyWireASLINK master station.
Transmission distance: the longest 200m.
Data input and output: up to 512 points.
Connect up to 128 units.
Enter 256 points, 256 points out of the output.
Connecting the input and output of the sensor to the programmable controller.
Ultra small sensor can be freely configured to control the input and output of 512 points LX10-CM PDF.
In addition, the sensor can be supplied with a AnyWireASLINK transmission line (2 lines) by means of communication,
So as to facilitate additional sensor
LX10-CM
And can also be through the engineering software Works2 GX batch management sensor disconnection detection and from the station module settings, etc.,
Can significantly reduce the engineering hours LX10-CM PDF.
Basic composition.
AnyWireASLINKAnyWireASLINK can be selected according to the load current of 2 wire or 4 wire from the station module.
In addition to the 2 wire type, the local power supply can be connected with the 4 wire type mixed use.
2 wire type.
The load current is less than that of the hour, by using the non isolated 2 wire type from the station module,
Easy connection without using local power supply LX10-CM PDF.
4 wire type
By using isolated 4 wire type from the station module, the local power supply can be used,
Can support the use of more current load. SSCNET III /H remote station.
Transmission speed: 150Mbps.
End cap.
Play the role of SSCNET III /H remote station
SSCNET III /H host module is the MELSEC-L series of input and output modules and intelligent function modules connected to the SSCNET III /H module.
Can be used as a remote station of motion controller,
The flexible configuration of I/O module and intelligent function module is realized,
Reduce device wiring, save space.
In addition, the module can be used for the input and output of the motion controller by the circulating transmission, and the module of the SSCNET III /H host module can be installed. Number of input channels: 4ch.
Input voltage: DC - 10 - 10V.
Input current: DC0 ~ 20mA.
Input voltage: 100 ~ 100mV / minute.
Input thermocouple: K, J, T, E, N, R, S, B, U, L, PL II, W5Re/W26Re.
Input temperature resistance: Pt1000, Pt100, JPt100, Pt50.
Conversion speed: 50ms/ch.
Resolution (voltage / current / micro voltage): 1/20000
Resolution (thermocouple): B, R, S, N, PL II, W5Re/W26Re:0.3,, K, E, J, T, U, L:0.1.
Temperature measuring resistance: Pt100, JPt100:0.03, /0.1, Pt1000, Pt50:0.1.
Reduce the programming time.
The digital output value can be easily converted (zoom) to any number of functions without the program.
No need to use ladder diagram conversion program, can reduce the programming time.
Zoom setting example (L60AD4-CM).
The digital output value (20000 ~ 0) of the input range 20mA ~ 4mA is scaled to the value of positive and negative 20000.
Digital filter function
Simply set the parameters, you can eliminate the functtion of the redundant frequency components LX10-CM datasheet.
Can be selected from low pass filter, high pass filter, medium pass filter.
No need to filter the ladder, can reduce programming time.
In addition, the conversion value of the A/D convertted by the filter can be obtained at the same time,
Therefore, the total processing time from the conversion to the filter processing can be shortened LX10-CM datasheet.