Analog input channel number: 4CH.
Available thermocouple: -.
Available temperature resistance: PT100, JPt100.
Sampling period 4CH: 250ms/500ms.
Control output cycle: 0.5s ~ 100.0s.
Input impedance: 1M.
Input filter (0: input filter OFF): 0 ~ 100s.
Sensor compensation value setting: the full range of the input range of the negative terminal to the full range of the input range R32MTCPU PDF.
Sensor input when the action: according to the scale of the processing
R32MTCPU
Temperature control mode: ON/OFF PID pulse or 2 position control
Heater disconnection detection specification: there.
External wiring connection mode: 18 point screw terminal.
IQ-R MELSEC series of temperature control module to achieve a high stability and response to the temperature control R32MTCPU PDF.
Divided into Thermocouple Input, temperature resistance input two types of input,
These two kinds of input types are distinguished by the function of the detection of the broken line with / without heater.
Module binding function.
Combined with the use of up to 64 sets of temperature control module for temperature control. Can be combined with the function of the following two points R32MTCPU PDF.
Heating function between modules.
Peak current suppression function between modules.
By cooperating with the time of arrival of a number of loops, the average temperature is controlled.
Can realize the uniform temperature control, avoid partial burning control object,
Part of the phenomenon of thermal expansion. Can be divided into 16 groups, with its heating up to the time,
Reduce the overall system in heating up the waste of energy.
Peak current suppression function between modules
By the time staggered output transistor, suppressing peak current.
The power supply capacity of the equipment can be reduced by setting a larger channel and a smaller channel of the heater in the same set.
Can be divided into 5 groups. "Input points: 32 points.
Rated input voltage and frequency: DC24V.
Rated input current: TYP 4.0mA.
Response time: 0.1 ~ 70ms.
Common way: 32 point / public end.
Interrupt function: have.
External wiring connection mode: 40 pin connector.
The input and output module is the interface between the switch, sensor, actuator, and other control system of the ON/OFF signal processing.
Compared with the previous series, iQ-R MELSEC series of input and output modules have more features,
1 modules can be used for a variety of purposes, to help reduce the cost of deployment and maintenance costs.
The module design of the pursuit of convenience".
Paste the white label on the input module and paste the red label on the output module,
The rated specifications are clearly marked on the front of the module, which can prevent the use of errors.
The input and output number stamped on the top of the front display input and output module LED, can easiily confirm the status of the ON/OFF R32MTCPU datasheet.
The terminal arrangement of each signal is recorded on the wiring terminal of the 16 point module, and the false wiring can be prevented.
The 64 point module can be 32 points as the unit, throough the switch to switch to display the input and output number R32MTCPU datasheet.
In addition, serial number tag in the front of the module, can be easily recognized. "