Analog input channel number: 4CH.
Available thermocouple: -.
Available temperature resistance: PT100, JPt100.
Sampling period 4CH: 250ms/500ms.
Control output cycle: 0.5s ~ 100.0s.
Input impedance: 1M.
Input filter (0: input filter OFF): 0 ~ 100s.
Sensor compensation value setting: the full range of the input range of the negative terminal to the full range of the input range RX41C4 PDF.
Sensor input when the action: according to the scale of the processing
RX41C4
Temperature control mode: ON/OFF PID pulse or 2 position control
Heater disconnection detection specification: none.
External wiring connection mode: 18 point screw terminal.
IQ-R MELSEC series of temperature control module to achieve a high stability and response to the temperature control RX41C4 PDF.
Divided into Thermocouple Input, temperature resistance input two types of input,
These two kinds of input types are distinguished by the function of the detection of the broken line with / without heater.
Module binding function.
Combined with the use of up to 64 sets of temperature control module for temperature control. Can be combined with the function of the following two points RX41C4 PDF.
Heating function between modules.
Peak current suppression function between modules.
Temperature rising function between modules
By cooperating with the time of arrival of a number of loops, the average temperature is controlled.
Can realize the uniform temperature control, avoid partial burning control object,
Part of the phenomenon of thermal expansion. Can be divided into 16 groups, with its heating up to the time,
Reduce the overall system in heating up the waste of energy. 1Gbps, master / local station.
IE Field CC-Link network is a kind of field network based on Gigabit Ethernet,
Integrated control of the controller, I/O control, safety control, motion control, can carry out a full range of control.
According to the production line, equipment, equipment layout, the star, linear and ring topology of flexible wiring.
Building a flexible network
Star topology
Star connection is carried out among the modules by using switching hubs.
When using star topology, you can easily add from the station.
Linear topology
Between the modules to carry out a linear connection.
Distribution cost can be reduced.
Ring topology
Ring connection in between each module.
Part of the anomaly occurs from the station, can be through the ring back function,
Use only normal station to contiinue data link RX41C4 datasheet.
Support IE Field CC-Link network synchronous communication function
According to the synchronization period specified by the master station, the control period of the slave station is synchronized by the IE Field CC--Link network RX41C4 datasheet.
According to this, the action time of the station can be synchronized with other slave stations which are connected on the same network.