Terminals: Push-In Plus terminal blocks.
Type: Input *1.
Points: 16.
Internal I/O circuit common: NPN (– common).
Rated voltage: 24 VDC.
I/O Relay Terminals with 16 Points and,
Push-In Plus terminal blocks to,
Downsize Control Panels and Save Labor.
I/O Relay Terminals with 16 points to mount G2RV Slim I/O Relays GT1-OD16-1 PDF.
Push-In Plus terminal blocks are used to save wiring work in,
comparison with traditional screw terminals
GT1-OD16-1 (Wiring time is,
reduced by 60%* in comparison with traditional screw terminals.).
Work is reduced ever further with one-step cable connection to the PLC.
Diode provided for coil surge absorption.
Operation indicators for immediate recognition of I/O signal status GT1-OD16-1 PDF.
Accepts G3RV Slim I/O SSRs.
DIN Track or screw mounting. Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max GT1-OD16-1 PDF.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal iis provided for,
each connector GT1-OD16-1 datasheet.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software GT1-OD16-1 datasheet.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.