Number of phases: Three-phase.
Insulation method: Phototriac coupler.
Operation indicator: Yes (yellow).
Rated input voltage: 12 to 24 VDC.
Zero cross function: Yes.
Type: DIN track mounting *2.
Applicable load: 25 A, 200 to 480 VAC.
Number of pole: 3.
Compact, Slim-profile SSRs with Heat Sinks GX-DA0271 PDF.
Solid State Contactors for Three-phase.
Heaters Reduced Installation Work.
with DIN Track Mounting
GX-DA0271
RoHS compliant.
Surge pass protection improved surge dielectric strength,
for output currents. (OMRON testing).
Slim design with 3-phase output and built-in heat sinks.
DIN Track mounting types and screw mounting types are available.
All DIN Track mounting types mount to DIN Track.
(applicable DIN Track: TR35-15Fe (IEC 60715)) GX-DA0271 PDF.
Conforms to UL, CSA, and EN standards (TÜV certification). I/O classification: Counter Unit.
External I/O points: Inputs: 1, Outputs: 2.
I/O connections: Terminal block.
Operating mode: Linear counter.
A Counter Unit Supporting Encoder,
Input for Use with MULTIPLE I/O TERMINAL.
High-speed pulse with counting speed of 50 kHz.
Counting can be set to a multiplication factor of 1 or 4 GX-DA0271 PDF.
Wide range of measurement: -8,388,608 to 8,388,607.
One external input and two external outputs are available.
DIN track mounting. I/O classification: Relay output.
I/O points: 16.
I/O connections: M3 terminal block.
Power supply voltage: 24 VDC.
I/O specification: 2 A, SPST-NO.
Relay Output Unit Compatible with MULTIPLE I/O TERMINAL.
8- and 16-point relay output models are available.
Equipped with 8-point SSRs.
DIN track mounting.
Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal is provided for,
each connector GX-DA0271 datasheet.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software GX-DA0271 datasheet.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.