block for EtherCAT communicaitons.
changed by the setting with the switch.
facilitates the maintenance.
Moving average calculation function.
Settings within the range of 100μs-64ms.
Disconnection detection function.
switch and with tool software.
Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC) GX-DA0271 OMRON.
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0
GX-DA02715 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max GX-DA0271 OMRON.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors GX-DA0271 OMRON.
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance. Name: Compact Connectors.
Specifications: Outputs; 4 inputs; NPN.
Bit slave of smallest class in industry,
Innovation in wiring for any type of machinery.
Available in 2 typees: 2-point Bit Slave Unit,
and 4-point Bit Slave Unit GX-DA0271.
Compact size for installation in limited space.
Save space and wiring since bit slave can be,
installed near I/O devices.
Industry first bit slave connectable with round,
cabless which can be easily purchased at a lower price GX-DA0271.
Connectable with flat cables, too for easy wiring.
Cables are selectable depending on applications.