FX1S can not do N:N network master
Time: 3/30/2017 9:03:56 AM
I am in tgineering FX1S has FX1S 3 sets of MITSUBISHI PLC are FX1S, FX1N, and FX2N, FX1N and FX1S respectively using FX1N-485BD, FX2N FX2N-485BD, N:N network, originally wanted to make FX1S when the master, because he is away from the control room recently, but by programming the D8176-8180 FX1S after the assignment, in any case do not initiate communication. The same program is downloaded to the FX2N, some of the normal communication, difficult
Re: Time: 3/30/2017 9:26:00 AM
When the system contains FX1S, FX0N programmable controller, please be sure to set the refresh range mode 0.
When set to mode 0, all FX1S, FX0N programmable controller in the system will have a data transfer sequence error. Moreover, the link time will be extended, so be sure to pay attention.
FX1S can also do N:N network master.
Thank you for MITSUBISHI motor automatic
Re:Re: Time: 3/30/2017 11:50:00 AM
Should be set to 0, and now is to do the normal communication from the station, FX1S do the master is not to send data, send and receive are not flashing
Re:Re:Re: Time: 3/30/2017 4:38:00 PM
Should be set to 0, and now is to do the normal communication from the station, FX1S do the master is not to send data, send and receive are not flashing
Re:Re:Re:Re: Time: 3/30/2017 7:02:00 PM
FX1S can do a master, just download a few times actually began to send, wonder, something strange, do not know what the reason.
Re:Re:Re:Re:Re: Time: 3/30/2017 11:50:00 PM
If you have problems again, you can leave a message, or call our technical support hotline 400--.