LK166
Home >> Products >> OMRON >> Master slave station products >> CompoNet >> CompoNet Gateway Unit for CC-Link CRT1-OD16SL OMRON CRT1-OD16SL

CompoNet Gateway Unit for CC-Link CRT1-OD16SL OMRON CRT1-OD16SL

Brand: OMRON
Name: CompoNet Gateway Unit for CC-Link
Model: CRT1-OD16SL
Name: Clamp Terminal Blocks.
Specifications: Outputs; 16 outputs ; NPN; --.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error.

Name: MIL Connectors.
Specifications: Outputs; 16 outputs ; PNP; --.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system.
A wide variety of CompoNet Slave Units,
contribute to system size reduction OMRON CRT1-OD16SL.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site CRT1-OD16SL
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error. Specifications: Input, NPN (+ common), 16 points.
I/O connections: Sensor I/O connector.
Rated internal circuit power supply voltage:
Supplied from the communications connector OMRON CRT1-OD16SL.
Rated I/O power supply voltage: Supplied from the communications connector.
Environment-resistive (IP67) I/O.
Terminals with Troubleshooting.
Functions such as Sensor Power.
Supply Short-circuit Detection.
Equipped with the standard Smart Slave functions that provide powerful,
preventative maintenance and troubleshooting capabilities OMRON CRT1-OD16SL.
High degree of environmental resistance with dust-proof,
and drip-proofconstruction.
Power supply wiring is not required for input devices.
Connect heavy-load devices (up to 1.5 A).
Power supply wiring is not required for input devices such as sensors CRT1-OD16SL OMRON.
(Power supply wiring is required for output devices.)
Detects ground faults or disconnects and notifies the Master CRT1-OD16SL OMRON.
Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3 CRT1-OD16SL OMRON. 0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminaal is provided for,
each connector CRT1-OD16SL.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software OMRON CRT1-OD16SL.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.


...More relevant models >>>>