Analog input channel number: 4CH.
Available thermocouple: B, R, S, K, E, J, T, N, U, L, PL II, W5Re/W26Re.
Available temperature resistance: PT100, JPt100.
Sampling period 4CH: 250ms/500ms.
Control output cycle: 0.5s ~ 100.0s.
Input impedance: 1M.
Input filter (0: input filter OFF): 0 ~ 100s.
Sensor compensation value setting: the full range of the input range of the negative terminal to the full range of the input range R38B PDF
R38B
Sensor input when the action: according to the scale of the processing.
Temperature control mode: ON/OFF PID pulse or 2 position control
Heater disconnection detection specification: none.
External wiring connection mode: 18 point screw terminal.
IQ-R MELSEC series of temperature control module to achieve a high stability and response to the temperature control R38B PDF.
Divided into Thermocouple Input, temperature resistance input two types of input,
These two kinds of input types are distinguished by the function of the detection of the broken line with / without heater.
Reduce the incidence of non qualified products by inhibiting the effect of external interference,
Improve the efficiency of life and product quality by using external interference suppression function,
The temperature fluctuation caused by external disturbance can be rapidly attenuated,
To ensure that the product processing within the specified temperature range, reduce the incidence of substandard products R38B PDF.
This function is very effective for the product packaging machine and injection molding machine, the semiconductor manufacturing device of the wafer heating board and so on. 10Mbps Max., master / local station, support Ver.2 CC-Link.
CC-Link is a bus (RS-485) - type open field network which can control and information processing at the same time.
Can be in the CC-Link and high-speed transmission of ON/OFF information from the station equipment, such as bit data, analog information, such as digital data R38B datasheet.
Connect all kinds of field equipment through CC-Link.
Can connect all kinds of support CC-Link field equipment, according to vvarious control requirements to build the corresponding system R38B datasheet.
Use remote device network mode, up to 64 remote equipment such as analog devices, etc..