Brand: MITSUBISHI
Product model: R60AD8-G
Name: Analog input module
Sort: PDF datasheet
File language: English
File size: 42.57MB
The input power supply voltage: AC100 ~ 240V.
Input frequency: 50/60Hz plus or minus 5%.
Input maximum apparent power: 160VA.
Maximum input power: -.
Rated output current (DC5V): 9A.
Rated output current (DC24V): -.
IQ-R MELSEC series consists of CPU module, power module, substrate module, input and output module, intelligent function module and so on R60AD8-G PDF.
For the entire system, the substrate module can be expanded to 7 levels, up to 64 modules can be installed,
Therefore, large scale system can be constructed R60AD8-G In addition, by using the RQ extended substrate module,
The sea can also effectively use the MELSEC-Q series of modules of the asset. "Operation control mode: stored procedure repeated operation R60AD8-G PDF.
Built in IE CC-Link.
Input / output points: 4096 points.
Program capacity: 40K.
Increase the speed of a constant cycle interrupt program.
Perform a minimum interval constant period interrupt program can be shortened to 50 s,
Programmable logic controller can read more high-speed signals.
In addition, the interrupt routine can be set priority, and the interrupt program with high priority is executed when the interrupt processing is interrupted R60AD8-G PDF.
Therefore, when the signal is read at a high speed, the program can read the signal from the constant cycle of the conventional input module +CPU module.
Soft element / label area for easy processing
The extended SRAM card is installed on the programmable controller CPU module,
Soft element / label storage area with up to 5786K words.
The expansion area is connected to the memory of the built-in CPU module,
The range of soft components / labels can be freely distributed.
Therefore, it can be easily programmed without taking into account the boundaries of each storage area.
In addition, can also use the SD memory card processing records data, database data, such as large capacity data. Analog input channel number: 8CH.
Cold end compensation accuracy: plus or minus 1.
Available thermocouple: B, R, S, K, E, J, T, N.
Available temperature resistance: -.
Resolution 1:B, R, S, N:0.3
Resolution 2:K, E, J, T:0.1
Conversion speed: 30ms/CH.
Insulation between channels: isolation transformer insulation.
Disconnection detection: there.
External wiring connection mode: 40 pin connector.
output
The temperature measurement value (16 bit''signed binary): 2700 ~ 18200.
Zoom value (16 bit with symbol binary).
High speed data sampling is not affected by the scan time.
The analog input module has the function of recording, which can be used to collect the analog quantity input data in the industrial application.
Can continuously collect data in a set period, each channel can store up to 10000 points of the recorded data.
In addition, the state of the state of any time and data in the program can be changed as a trigger,
To stop collecting data. The analog quantity input data can be stored and maintained before and after the trigger state through the function,
Easy to determine the occurrence of the phenomenon and the collection of test data R60AD8-G datasheet. Such as motor testing equipment used in this function.
Control instructions from a programmablee controller to a transducer and a power meter transmission test mode,
At the same time, the test data of the test motor is collected at the same time R60AD8-G datasheet.
Related products
MITSUBISHI
Analog input module
R60AD4
MITSUBISHI Analog input module R60AD4
Analog input channel numer: 4CH. accuracy Am
MITSUBISHI
Temperature input module
R60RD8-G
MITSUBISHI Temperature input module R60RD8-G
Analog input channel numer: 8CH. Cold end co
MITSUBISHI
Analog input module
R60ADV8
MITSUBISHI Analog input module R60ADV8
Analog input channel numer: 8CH. accuracy Am