Type: sensor connector (e-CON).
Input form: DC input, negative public end.
Input points: 16 points.
Rated input voltage / current: DC24V (4mA).
External connection: 3 wire.
IE CC-Link field network module type remote unit.
Select input response time from 0ms/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms.
High speed input and output control of single module can be realized by using first order logic function
A9GT-50WPSC
IE CC-Link field network remote equipment station. According to the equipment, more easily distributed input and output devices.
Can be connected to the expansion module, more convenient to expand the input and output points.
Support synchronous communication (using with simple motion control module) A9GT-50WPSC.
According to the simple motion control module of the network (Master) control cycle of the implementation of the control cycle and its synchronization,
Implementation of multiple simultaneous action from the station. MITSUBISHI inverter FR-D740 series.
Voltage level: three phase 400V.
Frequency converter capacity: 1.5KW.
The internal and back of the inverter structure considering the cooling effect, the relationship between the upper and lower ventilation is also important,
Therefore, in order for the type of unit, hanging on the wall to the vertical position, the installation of vertical as possible A9GT-50WPSC.
Transducer can be used to drive a single phase motor? Can single phase power supply be used?
Basically can not be used. For a single phase motor with governor switch, the auxiliary winding will be burnt when the speed is below the operating point;
For the capacitor start or capacitor operation mode, the capacitor explosion will be induced.
The inverter power supply is usually 3, but the capacity for small, single-phase power is also useful functioning aircraft. MITSUBISHI motor universal AC servo amplifier MELSERVO-J3 series.
Rated output: 5.0kw.
Interface type: SSCNET type III fiber communication.
Special features: integrated driver security.
Power specification: three phase AC200V.
STO function as a security feature is added to the SSCNET III fiber communication type servo amplifier.
By using the STO function, the electromagnetic contactor used in the past to prevent the motor from accidentally starting is no longer needed.
SS1 functions can be realized by using the MR-J3-D05 security logic unit.
MR-J3-BS uses a full closed loop control systemm A9GT-50WPSC.
Compatibility with MR--J3-B .
MR-J3-BS installation, wiring and connectors are the same as the MR-J3-B, so do not change the existing connection will be easy to MR-J3-B
Change to MR-J3-BS.
Security functions are connected to the CN8 interface through an external securityy ccircuit to increase the MR-J3-BS driver security A9GT-50WPSC.
Compatible full closed loop control system.
MR-J3-BS has a full closed loop control system version.