Unit type: CJ1 CPU Bus Units.
Units with EtherCAT interface.
EtherCAT communications.
No. of axes: 16 axes.
No. of unit numbers allocated: 1.
Current consumption : 5V, 0.46A; 24V,--.
Standards: UC1, CE.
improve the production efficiency.
and accurate position control.
this position control unit.
Unit type: CJ1 Basic I/O Units.
Product name: Quick-response Input Unit.
Specifications: I/O points, 16 inputs;
Input voltage current, 24VDC, 7mA;
Commons: 16 points, 1 common;
Input pulse widt conditions, ON time:
0.05 ms max. OFF time: 0.5 ms max;
Max. Units mountable per Unit, 2;
External connection, Removable terminal block CJ1W-NCF82 OMRON.
No. of words allocated: 1 word.
Current consumption: 5V, 0
CJ1W-NCF8208A; 24V, --.
Standards: UC1, N, L, CE.
Capture Input Signals Shorter,
Than the Cycle Time.
This Input Unit can read pulse inputs that,
are shorter than the cycle time of the CPU Unit. Unit type: CJ1 Special I/O Units.
Product name: Analog Output Unit.
I/O points: 2 outputs;
Signal range selection:
Set separately for each output CJ1W-NCF82 OMRON.
Signal range, Resolution: 1 to 5 V,
0 to 5 V, 0 to 10 V, -10 to 10 V,
4 to 20 mA; 1/4,00.
Conversion period: 1 ms/point.
Accuracy at ambient temperature of 25°C:
Voltage: ±0.3% of F.S. Current: ±0.5% of F.S.
External connection: Removable terminal block.
External power supply: 24 VDC +10% -15%, 140mA max.
No. of unit numbers allocated: 1 CJ1W-NCF82 OMRON.
Current consumption: 5V, 0.12A; 24V, 0.14*3.
Standards: UC1, N, L, CE.
Consistent Microsecond Throughput:
Models with Direct Conversion Join the Lineup.
Analog Input Units for converting analog input,
signals into binary data.
Analog Output Units for converting binary ,
data into analog output signals. Unit classification: CJ1 Special I/O Units.
Product name: Process Input Units,
(Isolated type Units with Universal Inputs).
Input points: 4 inputs.
Signal range selection:
Set separately for each input.
Signal range:Fully universal
inputs: Pt100, JPt100, Pt1000, K,
J, T, L, R, S, B, 4 to 20 mA, 0 to 20 mA,
1 to 5 V, 0 to 5 V, 0 to 10 V.
Conversion speed (resolution): Conversion,
speed: 250 ms/4 inputs.
Accuracy at ambient temperature of 25°C:
Accuracy: Platinum resistance thermometer,
input: ±0.3% of PV or ±0.8°C, whichever,
is larger) ±1 digit max. Thermocouple input:
(±0.3% of PV or ±1.5°C, whichever is larger),
±1 digit max. *1 Voltage or current input:
±0.3% of F.S. ±1 digit max.
External connection: Removable terminal block.
No. of unit numbers allocateed: 1 CJ1W-NCF82.
Current consumption: 5V, 0.32A; 24V, --.
Standards: UC1, L, CE.
A Single Unit Handling All Types of Inputs,
such as Temperature Sensor Inputs and,
Analog Signal Inputs (e.g., 4 to 20 mA or 1 to 5V).
A Unit supports four inpuut channels,
each of which can be set to a
platinum resistance thermometer, thermocouple,
and DC signal (current, voltage) CJ1W-NCF82.
All inputs are isolated.