LK166
Home >> Products >> OMRON >> Master slave station products >> EtherCAT remote I/O terminal >> GX-OD1611 | OMRON EtherCAT Remote I/O Terminals GX-OD1611

GX-OD1611 | OMRON EtherCAT Remote I/O Terminals GX-OD1611

Brand: OMRON
Name: EtherCAT Remote I/O Terminals
Model: GX-OD1611
Input capacity: 16 points.
Rated current (ON current):
0.5 A/output, 4.0 A/common.
Internal I/O common: NPN.
Residual voltage: 1.2 V max.
(0.5 ADC, between each output,
terminal and the G terminal).
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common: 16 points/common.
Output indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit.)
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance.

Internal I/O common: PNP.
I/O indicators: LED display (yellow).
Unit power supply current consumption: 120 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available at input,
section only (Operates at 50 mA/point min OMRON GX-OD1611. )
Easy wiring using industry standard,
e-CON connectors GX-OD1611
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
switch and with tool software OMRON GX-OD1611.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance. Input capacity: 32 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min. (between each in,
put terminal and the V terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the V terminal) OMRON GX-OD1611.
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0 GX-OD1611 OMRON. 5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 32 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation GX-OD1611 OMRON.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 230 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 220 g max.
Expansion functions: No GX-OD1611 OMRON.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common termiinal is provided for,
each connector GX-OD1611.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software OMRON GX-OD1611.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.


...More relevant models >>>>