I/O classification: Output.
Internal I/O circuit common: PNP (+ common).
I/O points: 16.
Rated voltage: 24 VDC.
I/O rated voltage: 24 VDC.
(Long-distance/High-speed Communications Selection).
(W x H x D) mm for 16-point terminals.
because the I/O terminals are insulated from the internal circuits.
DIN track mounting and screw mounting are both supported.
Name: Compact Connectors.
Specifications: Inputs/Outputs; 2 input/2 output; NPN.
Bit slave of smallest class in industry,
Innovation in wiring for any type of machinery.
Available in 2 types: 2-point Bit Slave Unit,
and 4-point Bit Slave Unit.
Compact size for installation in limited space.
Save space and wiring since bit slave can be,
installed near I/O devices OMRON SRT2-OD16-1.
Industry first bit slave connectable with round,
cables which can be easily purchased at a lower price
SRT2-OD16-1
Connectable with flat cables, too for easy wiring.
Cables are selectable depending on applications. Specifications: Outputs, PNP (+ common), 32 outputs.
I/O connections: MIL connector.
Rated internal circuit power supply voltage:
Supplied from communications connector OMRON SRT2-OD16-1.
Rated I/O power supply voltage: 24 VDC.
First Board-type Terminals for Smart Slaves!
Easily modified to handle an array of I/O interfaces,
and eliminates much on-site wiring.
User boards attach easily to the DRT2-@D32BV(-1) using screws. Input capacity: 32 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min. (between each in,
put terminal and the V terminal) OMRON SRT2-OD16-1.
OFF voltage: 5 VDC max. (between each in,
put terminal and the V terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0 SRT2-OD16-1 OMRON. 1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 32 points/common SRT2-OD16-1 OMRON.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 230 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times SRT2-OD16-1 OMRON.
Weight: 220 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminaal is provided for,
each connector SRT2-OD16-1.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software OMRON SRT2-OD16-1.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.