Analog input channel number: 4CH.
Available thermocouple: -.
Available temperature resistance: PT100, JPt100.
Sampling period 4CH: 250ms/500ms.
Control output cycle: 0.5s ~ 100.0s.
Input impedance: 1M.
Input filter (0: input filter OFF): 0 ~ 100s.
Sensor compensation value setting: the full range of the input range of the negative terminal to the full range of the input range R120ENCPU PDF.
Sensor input when the action: according to the scale of the processing
R120ENCPU
Temperature control mode: ON/OFF PID pulse or 2 position control
Heater disconnection detection specification: none.
External wiring connection mode: 18 point screw terminal.
IQ-R MELSEC series of temperature control module to achieve a high stability and response to the temperature control R120ENCPU PDF.
Divided into Thermocouple Input, temperature resistance input two types of input,
These two kinds of input types are distinguished by the function of the detection of the broken line with / without heater.
Module binding function.
Combined with the use of up to 64 sets of temperature control module for temperature control. Can be combined with the function of the following two points R120ENCPU PDF.
Heating function between modules.
Peak current suppression function between modules.
Temperature rising function between modules
By cooperating with the time of arrival of a number of loops, the average temperature is controlled.
Can realize the uniform temperature control, avoid partial burning control object,
Part of the phenomenon of thermal expansion. Can be divided into 16 groups, with its heating up to the time,
Reduce the overall system in heating up the waste of energy. Operation control mode: stored procedure repeated operation.
Built in IE CC-Link.
Input / output points: 4096 points.
Program capacity: 80K.
Increase the speed of a constant cycle interrupt program.
Perform a minimum interval constant period interrupt program can be shortened to 50 s,
Programmable logic controller can read more high-speed signals.
In addition, the interrupt routine can be set priority, and the interrupt program with high priority is executed when the interrupt processing is interrupted.
Therefore, when the signal is read at a high speed, the program can read the signal from the constant cycle of the conventional input module +CPU module.
Data management using database functions.
Data and production performance data through computer management in the past can be managed by database management of a built-in programmable controller.
Database can be created in the SD memory card, and can use the special instructions to easily add, updatte, retrieve, delete data R120ENCPU datasheet.
In addition, the database can be imported and exported through the Unicode text file format,
Share data with spreadsheet software. In particular, can be flexibly used in the production of many varietiess of food and beverage production line and other fields,
Effectively carry out the change of formula data and the management of production performance R120ENCPU datasheet.