Brand:
OMRON
Name: Digital I/O Terminal 3-tier Terminal Block Type
Model: GX-ID1628
Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.
Classification: For input.
Internal I/O circuit common: NPN (– common).
I/O points: 8 input points.
Connector Connection Models that.
Allows Easy Connection to Sensors and Output Devices.
Sensors with easy-to-wire connectors are easily,
attached or detached.
Connects to 2-wire sensors.
Remote teaching of the Sensor Terminal is possible OMRON GX-ID1628.
with the PLC by using output signals of the Sensor Terminal GX-ID1628
DIN track mounting and screw mounting are available. Unit: Terminal block model.
I/O classification: Digital input.
Internal I/O common: PNP (- common).
I/O points: 16.
I/O connections: M3 terminal board.
Power supplyvoltage: 24 VDC.
I/O specification: DC/transistor.
Digital I/O Units Compatible with MULTIPLE I/O TERMINAL,
Terminal block, connector, and high-density connector,
models are available OMRON GX-ID1628.
The circuit block of the terminal block model can be,
mounted or dismounted for ease of maintenance without,
disconnecting the wires.
DIN track mounting. I/O classification: Input.
Internal I/O circuit common: NPN (+ common).
I/O points: 8.
Rated voltage: 24 VDC.
I/O rated voltage: 24 VDC OMRON GX-ID1628.
Long-distance Communications Supported by SRT2 Models,
(Long-distance/High-speed Communications Selection).
Ultra-compact at 80 x 48 x 50 (W x H x D) mm for,
4-point and 8-point terminals and 105 x 48 x 50,
(W x H x D) mm for 16-point terminals GX-ID1628 OMRON.
Two independent power supplies can be used,
because the I/O terminals are insulated from the internal circuits GX-ID1628 OMRON.
DIN track mounting and screw mounting are both supported. Name: Two-tier Screw Terminal Block.
Specifications: Inputs; 8 inputs; NPN.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost can be reduced. GX-ID1628.
Bit-level I/O distribution reduces,
wiring in the system GX-ID1628 OMRON.
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on sitee OMRON GX-ID1628.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error.